Connecting between the frequency convertor and the motor for power circuits in machine cabling. In dry damp or wet interiors with normal mechanical stress conditions For outdoor usage within the permitted range of temperature.
Technical Data
Adapted to VDE 0250 / 0281 / 0282
U0/U 600/1000V. Control cores 250V
Min. 20 GΩ x cm
Flexing -5°C to +70°C. Fixed installation -30°C to +70°C
Flexing 12 x cable ø. Fixed installation 4 x cable ø
Supply cores: C/C 4000V & C/S: 2000 V
C/C: 1500 V, C/S: 750 V
Cable Construction
Bare copper, fine wire conductors according to EN 60228 cl. 6.
Core insulation of special PVC or TPE (control cores).
Control pairs screened with laminated film and braided with a layer of tinned-copper wires.
Cores and pairs are twisted together.
Non woven wrapping.
Extruded PUR outer sheath grey (RAL 7001).
Properties
Flame retardant according to EN 60332-1-2.
The version with special TPE insulation ensures low mutual capacitance, lower dielectric loss, low screen interference currents.
Meets EMC requirements.
Due to the optimal screening an interference-free operation of frequency converters is obtained.
UV resistant to ASTM G 154.
Cable Design Parameters
Kindly complete the part numbers for these cables by adding the suffix (in place of ‘y’) for the insulation material required:
1 – PVC 70°C, 9 – TPE
Part Number
No. of Cores & Nominal Cross Sectional Area (Sq. mm)