2XY/2XFY/2XWY-1.5 Sq. mm Control Cable

2XY/2XFY/2XWY-1.5 Sq. mm
2XY/2XFY/2XWY-1.5 Sq. mm Cross
  • REACH
  • RoHS

2XY/2XFY/2XWY-1.5 Sq. mm Control Cable

Application

These control cables are designed for use in control circuits in industrial, commercial, and residential applications, providing reliable signal transmission with XLPE insulation and optional galvanised steel strip (2XFY) or wire (2XWY) armouring for enhanced mechanical protection, suitable for direct burial or exposed installations.

Standard

  • IS 7098 Part 1

Technical Data

  • 1.5 Sq. mm

Cable Construction

1.5 Sq. mm copper conductor, XLPE insulated, unarmoured (2XY) or galvanised steel strip/wire armoured (2XFY/2XWY) control cables as per IS 7098 Part 1.

  • Conductor: Copper conductor, solid (Class 1) or stranded (Class 2) as per IS 8130.
  • Insulation: Crosslinked polyethylene (XLPE).
  • Core Colors: Up to 5 cores by color coding; more than 5 cores with number printing as per IS 7098 Part 1.
  • Inner Sheath: PVC or PVC tape as per IS 7098 Part 1.
  • Armouring: Single armouring with galvanised steel strip (2XFY) or wire (2XWY).
  • Outer Sheath: PVC Type ST-2 as per IS 5831 (Options: FR Type, FRLS Type).
  • Cable Color: Black (Options: Any other color as per requirement).

Cable Design Parameters

While ordering, please specify the following details: Class of Conductor (Class 1 or 2) and Sheath Type (PVC Type ST-2, FR, or FRLS).

Part Number No. of Cores Nominal Thickness of Insulation (mm) Minimum Thickness of Inner Sheath (mm) Unarmoured (2XY) - Nominal Thickness of Outer Sheath (mm) Unarmoured (2XY) - Approx. Overall Diameter (mm) Unarmoured (2XY) - Approx. Net Weight of Cable (kg/km) Armoured with Flat Strips (2XFY) - Nominal Thickness of Arm. Strip (mm) Armoured with Flat Strips (2XFY) - Minimum Thickness of Outer Sheath (mm) Armoured with Flat Strips (2XFY) - Approx. Overall Diameter (mm) Armoured with Flat Strips (2XFY) - Approx. Net Weight of Cable (kg/km) Armoured with Round Wire (2XWY) - Nominal Diameter of Wire (mm) Armoured with Round Wire (2XWY) - Minimum Thickness of Outer Sheath (mm) Armoured with Round Wire (2XWY) - Approx. Overall Diameter (mm) Armoured with Round Wire (2XWY) - Approx. Net Weight of Cable (kg/km)
112300201105 2 0.7 0.7 1.8 10 140 N/A N/A N/A N/A 1.4 1.24 12.5 370
112300301105 3 0.7 0.7 1.8 10.5 160 N/A N/A N/A N/A 1.4 1.24 13.0 390
112300401105 4 0.7 0.7 1.8 11.5 200 N/A N/A N/A N/A 1.4 1.24 13.5 415
112300501105 5 0.7 0.7 1.8 12.5 225 N/A N/A N/A N/A 1.4 1.24 14.5 465
112300601105 6 0.7 0.7 1.8 13.5 250 N/A N/A N/A N/A 1.4 1.24 15.5 500
112300701105 7 0.7 0.7 1.8 13.5 260 N/A N/A N/A N/A 1.4 1.24 15.5 520
112301001105 10 0.7 0.7 1.8 17 340 N/A N/A N/A N/A 1.4 1.24 18.5 655
112301201105 12 0.7 0.7 1.8 17.5 390 N/A N/A N/A N/A 1.6 1.40 19.0 720
112301401105 14 0.7 0.7 1.8 18 430 N/A N/A N/A N/A 1.6 1.40 20.0 825
112301601105 16 0.7 0.7 1.8 18.5 475 0.8 1.40 19.0 750 1.6 1.40 21.0 925
112301901105 19 0.7 0.7 2.0 19.5 540 0.8 1.40 20.0 815 1.6 1.40 22.0 1010
112302401105 24 0.7 0.7 2.0 22.5 665 0.8 1.40 23.0 1000 1.6 1.40 25.0 1250
112302701105 27 0.7 0.7 2.0 23 750 0.8 1.40 23.5 1050 1.6 1.40 25.5 1330
112303001105 30 0.7 0.7 2.0 23.5 820 0.8 1.40 24.0 1125 1.6 1.40 26.0 1400
112303701105 37 0.7 0.7 2.0 26 665 0.8 1.40 26.0 1325 1.6 1.40 28.0 1550
112304001105 40 0.7 0.7 2.0 26 1050 0.8 1.40 26.5 1400 1.6 1.40 29.5 1700
112304401105 44 0.7 0.7 2.0 28 1150 0.8 1.40 28.5 1500 1.6 1.56 30.5 1850
112305201105 52 0.7 0.7 2.0 29 1300 0.8 1.56 30.5 1700 1.6 1.56 32.0 2050
112306101105 61 0.7 0.7 2.2 31 1500 0.8 1.56 32.0 1950 2.0 1.56 34.5 2550
  • For conductor and resistance, refer to table no. 16-1.
  • For capacitance, reactance, and short circuit rating, refer to tables no. 16-5, 16-6, and 16-7.
  • For current rating, refer to table no. 16-8.

Electrical Parameters

Electrical parameters such as conductor resistance, capacitance, reactance, short circuit rating, and current rating are available in referenced tables (16-1, 16-5, 16-6, 16-7, 16-8). Please contact us for detailed specifications.