EAXVB Cable

EAXVB Cable
EAXVB Cable Cross

EAXVB Cable

Application

Power distribution cable with aluminium conductor suitable for low voltage applications in power plants, transformer stations, industrial plants, metropolitan networks, and other electric plants with heavy current and thermal loads. Ideal for fixed installations in ground, canals, concrete, and areas free from heavy mechanical stress.

Standard

  • HD 603 Part 5/ Sect.A
  • IEC 60502-1

Technical Data

  • 0.6/1.0 kV
  • -5°C to 90°C
  • 12x cable diameter

Cable Construction

  • Conductor: Aluminium conductor, Class 2 (SM).
  • Insulation: Cross-linked polyethylene (XLPE).
  • Core Colors: Blue, brown, black, grey.
  • Inner Sheath: Special bedding compound.
  • Outer Sheath: Special PVC, black.
  • Note: Waterproof variant (EXeVB) available with special water-blocking tape.

Cable Design Parameters

Part Number Nominal Cross-Sectional Area (mm²) Nominal Insulation Thickness (mm) Nominal Bedding Thickness (mm) Nominal Outer Sheath Thickness (mm) Approx. Overall Diameter (mm) Approx. Cable Weight (kg/km)
112801010091 4 x 25 0.9 1.0 1.8 24 695
112801020091 4 x 35 0.9 1.0 1.8 26 852
112801030091 4 x 50 1.0 1.0 1.9 29 1076
112801040091 4 x 70 1.0 1.2 2.0 34 1454
112801050091 4 x 95 1.1 1.2 2.2 38 1892
112801060091 4 x 120 1.2 1.4 2.3 43 2359
112801070091 4 x 150 1.4 1.4 2.5 47 2844
112801080091 4 x 185 1.6 1.4 2.6 52 3488
112801090091 4 x 240 1.7 1.6 2.9 59 4457

Electrical Parameters

Current carrying capacity for 4-core cables at specified conditions:

Nominal Cross-Sectional Area (mm²) In Ground at 30°C (Amp) In Air at 40°C (Amp)
25 95 99
35 116 117
50 140 140
70 170 176
95 200 221
120 225 258
150 255 294
185 285 339
240 325 402

Self-extinguishing and flame retardant according to IEC 60332-1-2. Voltage rating: 0.6/1.0 kV. Maximum conductor temperature: 90°C. CPR compliant; DOP available at Declaration of Performance. Please contact us for detailed specifications, including resistance, reactance, and short circuit ratings.