Halogen-free single-core wires are used for installation in dry environments for wiring up lighting fixtures and units where valuable assets are to be protected from further damage resulting from fire. These cables may be installed on, in and beneath plaster, as well as in closed installation ducts. The direct operating voltages is permitted up to 900 V against ground when they are used in rail-coaches. For the inner wiring of switch boards and distributors these are to be used with an alternating nominal voltage up to 1000V or a direct voltage up to 750V against ground.
BS EN 50525-3-41.
Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required:
01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – green/yellow, 07 – white, 08 – violet, 09 – brown, 10 – orange, 11 – pink,
12 – grey.
By adding the suffix (in place of ‘c’) for the conductor type required:
0 = Annealed Bare Copper (ABC), 1= Annealed Tinned Copper (ATC).
Part Numbers | Nominal Cross Sectional Area (Sq. mm) | Nominal Thickness of Insulation (mm) | Mean Overall Diameter | Approx. Cable Weight (kg/km) | ||
---|---|---|---|---|---|---|
Lower Limit (mm) | Upper Limit (mm) | |||||
H05Z-K | 02040101xx6c | 0.5 | 0.6 | 1.9 | 2.4 | 9 |
02040102xx6c | 0.8 | 0.6 | 2.1 | 2.6 | 12 | |
02040103xx6c | 1 | 0.6 | 2.2 | 2.8 | 15 | |
H07Z-K | 02040104xx6c | 1.5 | 0.7 | 2.8 | 3.5 | 21 |
02040105xx6c | 2.5 | 0.8 | 3.4 | 4.3 | 33 | |
02040106xx6c | 4 | 0.8 | 3.9 | 4.9 | 47 | |
02040107xx6c | 6 | 0.8 | 4.4 | 5.5 | 66 | |
02040108xx6c | 10 | 1.0 | 5.7 | 7.1 | 112 | |
02040109xx6c | 16 | 1.0 | 6.7 | 8.4 | 169 | |
02040110xx6c | 25 | 1.2 | 8.4 | 10.6 | 260 | |
02040111xx6c | 35 | 1.2 | 9.7 | 12.1 | 358 | |
02040112xx6c | 50 | 1.4 | 11.5 | 14.4 | 509 | |
02040113xx6c | 70 | 1.4 | 13.2 | 16.61 | 701 | |
02040114xx6c | 95 | 1.6 | 15.1 | 18.8 | 925 | |
02040115xx6c | 120 | 1.6 | 16.7 | 20.9 | 1168 | |
02040116xx6c | 150 | 1.8 | 18.6 | 23.3 | 1456 | |
02040117xx6c | 185 | 2.0 | 20.6 | 25.8 | 1773 | |
02040118xx6c | 240 | 2.2 | 23.5 | 29.4 | 2329 |
*Construction Product Regulation (CPR) is a regulation issued by the European Union with the purpose of regulating the limits of fire resistance and dangerous substances in the materials used in construction. This regulation applies to all products intended to be incorporated, permanently, in construction. Above link provides the DOP (declaration of performance) for the CPR compliance for the product.)