Fire Survival Cable IS 17505-1
Application
The cable is designed to have a robust halogen-free construction suitable to operate up to 1100V applications. This cable is suitable for wiring installations supplying critical loads requiring supply integrity for the required time period under fire situations. They ensure continued operation of vital circuits in the event of a fire outbreak.
Technical Data
Voltage Rating: 1100 Vac and 1500 Vdc
Operating Temperature Range: -5°C to 90°C (fixed installation)
Minimum Bending Radius: 12 x overall cable diameter
Cable Construction
Conductor: Electrolytic Annealed Plain / Tinned Copper (Class 1/2) as per IS 8130
Primary Insulation: Mica Tape Layer(s)
Secondary Insulation: Cross-linked PE (XLPE) / Cross-linked HFFR
Core Colors:
1 Core – Red, Black, Yellow, Blue, or Natural
2 Core – Red & Black
3 Core – Red, Yellow & Blue
4 Core – Red, Yellow, Blue & Black
5 Core – Red, Yellow, Blue, Black & Grey
6 Core and above – Number coded
Inner Sheath: Thermoplastic HFFR
Heat Barrier Tape (Optional): Glass Fibre Tape
Armour: Galvanized round wire for multicore & Non-Magnetic wires for single core
Sheath: Thermoplastic HFFR (HFS-TP 90) / Cross-linked HFFR (HFS-XL 90)
Properties
Halogen-Free Construction
Non-Toxic & Non-Corrosive
Self-Extinguishing and Flame Retardant
Maintains Long-Term Circuit Integrity
F3 / F30 / F60 / F120 FWS Compliant (F – Fire, W – Water, S – Mechanical Shock)
Cable Design Parameters
Please complete the part numbers for these cables by adding the suffix (in place of ‘z’) for the sheath color required: 1 – Black, 7 – Red.
Note: While ordering single core, color to be mentioned along with the part code.
Variant with Cross Linked Polyethylene (XLPE) Insulation
Part Number
No. of Cores
Nominal Cross Sectional Area (mm²)
Nom. Insulation Thickness (mm)
Approx. Overall Dia. (mm)
Approx. Cable Weight (kg/km)
DC Conductor Resistance at 20°C (Ω/km)
Current Rating (Ground at 30°C) (Amps)
Current Rating (Duct at 30°C) (Amps)
Current Rating (Air at 30°C) (Amps)
10050101009z
1
16
1
12
279.9
1.15
104
102
106
10050102009z
1
25
1.2
14
403.0
0.727
130
115
145
10050103009z
1
35
1.2
15
506.3
0.524
155
140
175
10050104009z
1
50
1.3
18
682.6
0.387
185
165
215
10050105009z
1
70
1.4
20
952.1
0.268
225
200
270
10050106009z
1
95
1.4
22
1212.6
0.193
265
235
330
10050107009z
1
120
15
54
3809.7
0.153
300
265
380
10050108009z
1
150
1.7
25
1761.9
0.124
335
300
430
10050109009z
1
185
1.9
28
2145.8
0.0991
380
335
495
10050110009z
1
240
2
31
2741.0
0.0754
435
385
590
10050111009z
1
300
2.1
34
3409.2
0.0601
490
430
670
10050112009z
1
400
2.4
37
4262.1
0.047
550
480
780
Cable Technical Data - 2 Core XLPE Insulation
Part Number
No. of Cores
Nominal Cross Sectional Area (mm²)
Nom. Insulation Thickness (mm)
Approx. Overall Dia. (mm)
Approx. Cable Weight (kg/km)
DC Conductor Resistance at 20°C (Ω/km)
Current Rating (Ground at 30°C) (Amps)
Current Rating (Duct at 30°C) (Amps)
Current Rating (Air at 30°C) (Amps)
10050113009z
2
1.5
0.7
15
370.2
12.1
33
25
29
10050114009z
2
2.5
0.7
18
524.2
7.41
43
33
39
10050115009z
2
4
0.7
19
594.8
4.61
51
37
44
10050116009z
2
6
0.7
21
781.4
3.08
63
46
56
10050117009z
2
10
0.7
23
914.3
1.83
88
62
75
10050118009z
2
16
0.7
23
1005.7
1.15
113
81
98
10050119009z
2
25
0.9
26
1329.5
0.727
144
109
131
10050120009z
2
35
0.9
27
1586.0
0.524
175
125
150
10050121009z
2
50
1
30
1926.0
0.387
206
161
194
10050122009z
2
70
1.1
34
2483.7
0.268
256
203
244
10050123009z
2
95
1.1
38
3301.3
0.193
300
239
288
10050124009z
2
120
1.2
41
3947.3
0.153
344
275
331
10050125009z
2
150
1.4
45
4704.4
0.124
388
316
381
10050126009z
2
185
1.6
49
5614.6
0.0991
438
364
438
10050127009z
2
240
1.7
55
6987.1
0.0754
506
425
512
10050128009z
2
300
1.8
60
8852.0
0.0601
562
482
581
10050129009z
2
400
2
66
10848.5
0.047
612
549
662
Cable Technical Data - 3 Core XLPE Insulation
Part Number
No. of Cores
Nominal Cross Sectional Area (mm²)
Nom. Insulation Thickness (mm)
Approx. Overall Dia. (mm)
Approx. Cable Weight (kg/km)
DC Conductor Resistance at 20°C (Ω/km)
Current Rating (Ground at 30°C) (Amps)
Current Rating (Duct at 30°C) (Amps)
Current Rating (Air at 30°C) (Amps)
10050130009z
3
1.5
0.7
15
391.9
12.1
25
19
22
10050131009z
3
2.5
0.7
18
579.0
7.41
35
32
33
10050132009z
3
4
0.7
19
712.0
4.61
44
37
39
10050133009z
3
6
0.7
21
879.5
3.08
55
47
50
10050134009z
3
10
0.7
23
1067.2
1.83
74
61
67
10050135009z
3
16
0.7
23
1214.8
1.15
94
78
85
10050136009z
3
25
0.9
26
1631.6
0.727
120
100
125
10050137009z
3
35
0.9
27
1977.8
0.524
145
120
155
10050138009z
3
50
1
30
2459.4
0.387
170
145
190
10050139009z
3
70
1.1
34
3394.0
0.268
210
175
235
10050140009z
3
95
1.1
38
4321.1
0.193
250
210
290
10050141009z
3
120
1.2
41
5216.4
0.153
285
240
330
10050142009z
3
150
1.4
45
6198.7
0.124
315
270
375
10050143009z
3
185
1.6
49
7531.1
0.0991
355
300
435
10050144009z
3
240
1.7
55
9853.2
0.0754
410
350
510
10050145009z
3
300
1.8
60
11920.6
0.0601
460
390
590
10050146009z
3
400
2
66
14679.5
0.047
520
440
670
Cable Technical Data - 3.5 Core XLPE Insulation
Part Number
No. of Cores
Nominal Cross Sectional Area (mm²)
Nom. Insulation Thickness (mm)
Approx. Overall Dia. (mm)
Approx. Cable Weight (kg/km)
DC Conductor Resistance at 20°C (Ω/km)
Current Rating (Ground at 30°C) (Amps)
Current Rating (Duct at 30°C) (Amps)
Current Rating (Air at 30°C) (Amps)
10050147009z
3.5
25
0.9
28
1810.0
0.727
120
100
125
10050148009z
3.5
35
0.9
30
2220.0
0.524
145
120
155
10050149009z
3.5
50
1
33
2850.0
0.387
170
145
190
10050150009z
3.5
70
1.1
38
3875.0
0.268
210
175
235
10050151009z
3.5
95
1.1
41
4880.0
0.193
250
210
290
10050152009z
3.5
120
1.2
45
5980.0
0.153
285
240
330
10050153009z
3.5
150
1.4
50
7300.0
0.124
315
270
375
10050154009z
3.5
185
1.6
55
8080.0
0.0991
355
300
435
10050155009z
3.5
240
1.7
62
11500.0
0.0754
410
350
510
10050156009z
3.5
300
1.8
67
13800.0
0.0601
460
390
590
10050157009z
3.5
400
2
74
16300.0
0.047
520
440
670
Cable Technical Data - 4 Core XLPE Insulation
Part Number
No. of Cores
Nominal Cross Sectional Area (mm²)
Nom. Insulation Thickness (mm)
Approx. Overall Dia. (mm)
Approx. Cable Weight (kg/km)
DC Conductor Resistance at 20°C (Ω/km)
Current Rating (Ground at 30°C) (Amps)
Current Rating (Duct at 30°C) (Amps)
Current Rating (Air at 30°C) (Amps)
10050158009z
4
1.5
0.7
17
548.8
12.1
25
19
22
10050159009z
4
2.5
0.7
19
698.8
7.41
35
32
33
10050160009z
4
4
0.7
21
866.3
4.61
44
37
39
10050161009z
4
6
0.7
22
1003.5
3.08
55
47
50
10050162009z
4
10
0.7
24
1247.5
1.83
74
61
67
10050163009z
4
16
0.7
26
1512.8
1.15
94
78
85
10050164009z
4
25
0.9
30
2105.9
0.727
120
100
125
10050165009z
4
35
0.9
32
2573.1
0.524
145
120
155
10050166009z
4
50
1
36
3434.5
0.387
170
145
190
10050167009z
4
70
1.1
41
4507.9
0.268
210
175
235
10050168009z
4
95
1.1
45
5676.0
0.193
250
210
290
10050169009z
4
120
1.2
49
6888.9
0.153
285
240
330
10050170009z
4
150
1.4
55
8691.4
0.124
315
270
375
10050171009z
4
185
1.6
60
10496.4
0.0991
355
300
435
10050172009z
4
240
1.7
68
13827.0
0.0754
410
350
510
10050173009z
4
300
1.8
74
16613.5
0.0601
460
390
590
10050174009z
4
400
2
82
20465.7
0.047
520
440
670
Cable Technical Data - Multi-Core (7-37 Cores) XLPE Insulation - 1.5 mm²
Part Number
No. of Cores
Nominal Cross Sectional Area (mm²)
Nom. Insulation Thickness (mm)
Approx. Overall Dia. (mm)
Approx. Cable Weight (kg/km)
DC Conductor Resistance at 20°C (Ω/km)
Current Rating (Ground at 30°C) (Amps)
Current Rating (Duct at 30°C) (Amps)
Current Rating (Air at 30°C) (Amps)
10050175009z
7
1.5
0.7
20
854.4
12.1
21
16
18
10050176009z
12
1.5
0.7
24
1188.6
12.1
17
13
15
10050177009z
16
1.5
0.7
26
1390.0
12.1
16
12
14
10050178009z
19
1.5
0.7
27
1530.2
12.1
15
11
13
10050179009z
27
1.5
0.7
32
1986.4
12.1
13
10
12
10050180009z
37
1.5
0.7
36
2669.4
12.1
11
9.5
10.5
Cable Technical Data - Multi-Core (7-37 Cores) XLPE Insulation - 2.5 mm²
Part Number
No. of Cores
Nominal Cross Sectional Area (mm²)
Nom. Insulation Thickness (mm)
Approx. Overall Dia. (mm)
Approx. Cable Weight (kg/km)
DC Conductor Resistance at 20°C (Ω/km)
Current Rating (Ground at 30°C) (Amps)
Current Rating (Duct at 30°C) (Amps)
Current Rating (Air at 30°C) (Amps)
10050181009z
7
2.5
0.7
22
956.2
7.41
27
21
15
10050182009z
12
2.5
0.7
27
1335.5
7.41
23
19.5
20.5
10050183009z
16
2.5
0.7
29
1552.2
7.41
20
18
19
10050184009z
19
2.5
0.7
31
1768.9
7.41
19
15
17
10050185009z
27
2.5
0.7
37
2519.9
7.41
17
14.5
14
10050186009z
37
2.5
0.7
41
3103.7
7.41
14.5
12.5
13
Variant with Cross Linked Halogen Free Flame Retardant (XL-HFFR) Insulation
Part Number
No. of Cores
Nominal Cross Sectional Area (mm²)
Nom. Insulation Thickness (mm)
Approx. Overall Dia. (mm)
Approx. Cable Weight (kg/km)
DC Conductor Resistance at 20°C (Ω/km)
Current Rating (Ground at 30°C) (Amps)
Current Rating (Duct at 30°C) (Amps)
Current Rating (Air at 30°C) (Amps)
10050101006z
1
16
1.2
13
306.4
1.15
104
102
106
10050102006z
1
25
1.3
14
428.6
0.727
130
115
145
10050103006z
1
35
1.3
17
577.1
0.524
155
140
175
10050104006z
1
50
1.4
18
715.1
0.387
185
165
215
10050105006z
1
70
1.5
21
998.9
0.268
225
200
270
10050106006z
1
95
1.5
22
1259.4
0.193
265
235
330
10050107006z
1
120
1.7
24
1534.2
0.153
300
265
380
10050108006z
1
150
1.9
26
1845.5
0.124
335
300
430
10050109006z
1
185
2.1
28
2239.7
0.0991
380
335
495
10050110006z
1
240
2.1
31
2837.9
0.0754
435
385
590
10050111006z
1
300
2.3
34
3545.2
0.0601
490
430
670
10050112006z
1
400
2.6
37
4420.6
0.047
550
480
780
Cable Technical Data - 2 Core XL-HFFR Insulation
Part Number
No. of Cores
Nominal Cross Sectional Area (mm²)
Nom. Insulation Thickness (mm)
Approx. Overall Dia. (mm)
Approx. Cable Weight (kg/km)
DC Conductor Resistance at 20°C (Ω/km)
Current Rating (Ground at 30°C) (Amps)
Current Rating (Duct at 30°C) (Amps)
Current Rating (Air at 30°C) (Amps)
10050113006z
2
1.5
0.8
16
496.7
12.1
33
25
29
10050114006z
2
2.5
0.8
17
555.6
7.41
43
33
39
10050115006z
2
4
0.8
19
661.3
4.61
51
37
44
10050116006z
2
6
0.8
21
805.6
3.08
63
46
56
10050117006z
2
10
0.9
23
986.4
1.83
88
62
75
10050118006z
2
16
0.9
22
1061.0
1.15
113
81
98
10050119006z
2
25
1
24
1408.0
0.727
144
109
131
10050120006z
2
35
1
26
1671.7
0.524
175
125
150
10050121006z
2
50
1.1
28
2026.1
0.387
206
161
194
10050122006z
2
70
1.2
32
2604.2
0.268
256
203
244
10050123006z
2
95
1.25
35
3419.9
0.193
300
239
288
10050124006z
2
120
1.4
38
4146.8
0.153
344
275
331
10050125006z
2
150
1.6
42
4940.8
0.124
388
316
381
10050126006z
2
185
1.8
46
5916.1
0.0991
438
364
438
10050127006z
2
240
1.8
51
7720.1
0.0754
506
425
512
10050128006z
2
300
2
55
9234.8
0.0601
562
482
581
10050129006z
2
400
2.2
61
11302.6
0.047
612
549
662
Technical Specifications - 3 Core XL-HFFR Insulated Cables
3 Core XL-HFFR Insulated Cables - Cross Linked Halogen Free Flame Retardant
Part Number
No. of Cores
Nom. Cross-Sectional Area (mm²)
Nom. Insulation Thickness (mm)
Approx. Overall Dia. (mm)
Approx. Cable Weight (kg/km)
DC Conductor Resistance @ 20°C (Ω/km)
Current Rating (Ground @ 30°C)
Current Rating (Duct @ 30°C)
Current Rating (Air @ 30°C)
10050130006z
3
1.5
0.8
17
546.9
12.1
25
19
22
10050131006z
3
2.5
0.8
18
617.4
7.41
35
32
33
10050132006z
3
4
0.8
20
811.1
4.61
44
37
39
10050133006z
3
6
0.8
22
928.5
3.08
55
47
50
10050134006z
3
10
0.9
24
1137.5
1.83
74
61
67
10050135006z
3
16
0.9
23
1284.6
1.15
94
78
85
10050136006z
3
25
1
26
1712.5
0.727
120
100
125
10050137006z
3
35
1
28
2066.3
0.524
145
120
155
10050138006z
3
50
1.1
31
2563.3
0.387
170
145
190
10050139006z
3
70
1.2
35
3527.5
0.268
210
175
235
10050140006z
3
95
1.25
38
4469.8
0.193
250
210
290
10050141006z
3
120
1.4
42
5424.6
0.153
285
240
330
10050142006z
3
150
1.6
46
6465.9
0.124
315
270
375
10050143006z
3
185
1.8
52
8278.9
0.0991
355
300
435
10050144006z
3
240
1.8
56
10156.1
0.0754
410
350
510
10050145006z
3
300
2
61
12319.6
0.0601
460
390
590
10050146006z
3
400
2.2
68
15875.8
0.047
520
440
670
Core with Cross Linked Halogen Free Flame Retardant (XL-HFFR) Insulation
Part Number
No. of Cores
Nominal Cross Sectional Area (mm²)
Nom. Insulation Thickness (mm)
Approx. Overall Dia. (mm)
Approx. Cable Weight (kg/km)
DC Conductor Resistance at 20°C (Ω/km)
Current Rating (Ground at 30°C) (Amps)
Current Rating (Duct at 30°C) (Amps)
Current Rating (Air at 30°C) (Amps)
10050101006z
1
16
1.2
13
306.4
1.15
104
102
106
10050102006z
1
25
1.3
14
428.6
0.727
130
115
145
10050103006z
1
35
1.3
17
577.1
0.524
155
140
175
10050104006z
1
50
1.4
18
715.1
0.387
185
165
215
10050105006z
1
70
1.5
21
998.9
0.268
225
200
270
10050106006z
1
95
1.5
22
1259.4
0.193
265
235
330
10050107006z
1
120
1.7
24
1534.2
0.153
300
265
380
10050108006z
1
150
1.9
26
1845.5
0.124
335
300
430
10050109006z
1
185
2.1
28
2239.7
0.0991
380
335
495
10050110006z
1
240
2.1
31
2837.9
0.0754
435
385
590
10050111006z
1
300
2.3
34
3545.2
0.0601
490
430
670
10050112006z
1
400
2.6
37
4420.6
0.047
550
480
780
Core with Cross Linked Halogen Free Flame Retardant (XL-HFFR) Insulation
Part Number
No. of Cores
Nominal Cross Sectional Area (mm²)
Nom. Insulation Thickness (mm)
Approx. Overall Dia. (mm)
Approx. Cable Weight (kg/km)
DC Conductor Resistance at 20°C (Ω/km)
Current Rating (Ground at 30°C) (Amps)
Current Rating (Duct at 30°C) (Amps)
Current Rating (Air at 30°C) (Amps)
10050113006z
2
1.5
0.8
16
496.7
12.1
33
25
29
10050114006z
2
2.5
0.8
17
555.6
7.41
43
33
39
10050115006z
2
4
0.8
19
661.3
4.61
51
37
44
10050116006z
2
6
0.8
21
805.6
3.08
63
46
56
10050117006z
2
10
0.9
23
986.4
1.83
88
62
75
10050118006z
2
16
0.9
22
1061.0
1.15
113
81
98
10050119006z
2
25
1
24
1408.0
0.727
144
109
131
10050120006z
2
35
1
26
1671.7
0.524
175
125
150
10050121006z
2
50
1.1
28
2026.1
0.387
206
161
194
10050122006z
2
70
1.2
32
2604.2
0.268
256
203
244
10050123006z
2
95
1.25
35
3419.9
0.193
300
239
288
10050124006z
2
120
1.4
38
4146.8
0.153
344
275
331
10050125006z
2
150
1.6
42
4940.8
0.124
388
316
381
10050126006z
2
185
1.8
46
5916.1
0.0991
438
364
438
10050127006z
2
240
1.8
51
7720.1
0.0754
506
425
512
10050128006z
2
300
2
55
9234.8
0.0601
562
482
581
10050129006z
2
400
2.2
61
11302.6
0.047
612
549
662
Core with Cross Linked Halogen Free Flame Retardant (XL-HFFR) Insulation
Part Number
No. of Cores
Nominal Cross Sectional Area (mm²)
Nom. Insulation Thickness (mm)
Approx. Overall Dia. (mm)
Approx. Cable Weight (kg/km)
DC Conductor Resistance at 20°C (Ω/km)
Current Rating (Ground at 30°C) (Amps)
Current Rating (Duct at 30°C) (Amps)
Current Rating (Air at 30°C) (Amps)
10050130006z
3
1.5
0.8
17
546.9
12.1
25
19
22
10050131006z
3
2.5
0.8
18
617.4
7.41
35
32
33
10050132006z
3
4
0.8
20
811.1
4.61
44
37
39
10050133006z
3
6
0.8
22
928.5
3.08
55
47
50
10050134006z
3
10
0.9
24
1137.5
1.83
74
61
67
10050135006z
3
16
0.9
23
1284.6
1.15
94
78
85
10050136006z
3
25
1
26
1712.5
0.727
120
100
125
10050137006z
3
35
1
28
2066.3
0.524
145
120
155
10050138006z
3
50
1.1
31
2563.3
0.387
170
145
190
10050139006z
3
70
1.2
35
3527.5
0.268
210
175
235
10050140006z
3
95
1.25
38
4469.8
0.193
250
210
290
10050141006z
3
120
1.4
42
5424.6
0.153
285
240
330
10050142006z
3
150
1.6
46
6465.9
0.124
315
270
375
10050143006z
3
185
1.8
52
8278.9
0.0991
355
300
435
10050144006z
3
240
1.8
56
10156.1
0.0754
410
350
510
10050145006z
3
300
2
61
12319.6
0.0601
460
390
590
10050146006z
3
400
2.2
68
15875.8
0.047
520
440
670
5 Core with Cross Linked Halogen Free Flame Retardant (XL-HFFR) Insulation
Part Number
No. of Cores
Nominal Cross Sectional Area (mm²)
Nom. Insulation Thickness (mm)
Approx. Overall Dia. (mm)
Approx. Cable Weight (kg/km)
DC Conductor Resistance at 20°C (Ω/km)
Current Rating (Ground at 30°C) (Amps)
Current Rating (Duct at 30°C) (Amps)
Current Rating (Air at 30°C) (Amps)
10050147006z
3.5
25
1
28
1950.0
0.727
120
100
125
10050148006z
3.5
35
1
30
2375.0
0.524
145
120
155
10050149006z
3.5
50
1.1
34
3060.0
0.387
170
145
190
10050150006z
3.5
70
1.2
38
4085.0
0.268
210
175
235
10050151006z
3.5
95
1.25
42
5120.0
0.193
250
210
290
10050152006z
3.5
120
1.4
47
6520.0
0.153
285
240
330
10050153006z
3.5
150
1.6
51
7700.0
0.124
315
270
375
10050154006z
3.5
185
1.8
57
7660.0
0.0991
355
300
435
10050155006z
3.5
240
1.8
62
12100.0
0.0754
410
350
510
10050156006z
3.5
300
2
68
14752.0
0.0601
460
390
590
10050157006z
3.5
400
2.2
76
18560.0
0.047
520
440
670
Core with Cross Linked Halogen Free Flame Retardant (XL-HFFR) Insulation
Part Number
No. of Cores
Nominal Cross Sectional Area (mm²)
Nom. Insulation Thickness (mm)
Approx. Overall Dia. (mm)
Approx. Cable Weight (kg/km)
DC Conductor Resistance at 20°C (Ω/km)
Current Rating (Ground at 30°C) (Amps)
Current Rating (Duct at 30°C) (Amps)
Current Rating (Air at 30°C) (Amps)
10050158006z
4
1.5
0.8
18
643.0
12.1
25
19
22
10050159006z
4
2.5
0.8
20
802.5
7.41
35
32
33
10050160006z
4
4
0.8
22
920.4
4.61
44
37
39
10050161006z
4
6
0.8
23
1061.8
3.08
55
47
50
10050162006z
4
10
0.9
25
1332.7
1.83
74
61
67
10050163006z
4
16
0.9
27
1618.8
1.15
94
78
85
10050164006z
4
25
1
30
2200.4
0.727
120
100
125
10050165006z
4
35
1
33
2695.0
0.524
145
120
155
10050166006z
4
50
1.1
37
3588.6
0.387
170
145
190
10050167006z
4
70
1.2
41
4669.4
0.268
210
175
235
10050168006z
4
95
1.25
46
5906.7
0.193
250
210
290
10050169006z
4
120
1.4
52
7679.5
0.153
285
240
330
10050170006z
4
150
1.6
56
9059.5
0.124
315
270
375
10050171006z
4
185
1.8
62
10991.4
0.0991
355
300
435
10050172006z
4
240
1.8
69
14224.7
0.0754
410
350
510
10050173006z
4
300
2
75
17214.8
0.0601
460
390
590
10050174006z
4
400
2.2
83
21257.9
0.047
520
440
670
lti-Core (7, 12, 16, 19, 27, 37) with 1.5 mm² Cross Linked Halogen Free Flame Retardant (XL-HFFR) Insulation
Part Number
No. of Cores
Nominal Cross Sectional Area (mm²)
Nom. Insulation Thickness (mm)
Approx. Overall Dia. (mm)
Approx. Cable Weight (kg/km)
DC Conductor Resistance at 20°C (Ω/km)
Current Rating (Ground at 30°C) (Amps)
Current Rating (Duct at 30°C) (Amps)
Current Rating (Air at 30°C) (Amps)
10050175006z
7
1.5
0.8
22
955.4
12.1
21
16
18
10050176006z
12
1.5
0.8
26
1348.9
12.1
17
13
15
10050177006z
16
1.5
0.8
28
1597.9
12.1
16
12
14
10050178006z
19
1.5
0.8
30
1788.8
12.1
15
11
13
10050179006z
27
1.5
0.8
35
2490.5
12.1
13
10
12
10050180006z
37
1.5
0.8
39
3081.7
12.1
11
9.5
10.5
lti-Core (7, 12, 16, 19, 27, 37) with 2.5 mm² Cross Linked Halogen Free Flame Retardant (XL-HFFR) Insulation
Part Number
No. of Cores
Nominal Cross Sectional Area (mm²)
Nom. Insulation Thickness (mm)
Approx. Overall Dia. (mm)
Approx. Cable Weight (kg/km)
DC Conductor Resistance at 20°C (Ω/km)
Current Rating (Ground at 30°C) (Amps)
Current Rating (Duct at 30°C) (Amps)
Current Rating (Air at 30°C) (Amps)
10050181006z
7
2.5
0.8
25
1028.1
7.41
27
21
15
10050182006z
12
2.5
0.8
29
1460.4
7.41
23
19.5
20.5
10050183006z
16
2.5
0.8
33
1650.0
7.41
20
18
19
10050184006z
19
2.5
0.8
35
1927.6
7.41
19
15
17
10050185006z
27
2.5
0.8
38
2745.9
7.41
17
14.5
14
10050186006z
37
2.5
0.8
42
3425.1
7.41
14.5
12.5
13
* up to 6 Sq mm circular stranded
10 Sq. mm stranded circular compacted
16 Sq. mm above stranded shaped compacted.
Note: The cable is also available with class 1 solid conductor