Uninyvin Cable

Uninyvin Cable
Uninyvin Cable Cross

Uninyvin Cable

Applications

These cables are used in UPS systems and server rooms as the nylon and fiberglass braid on the cable does not allow the heat generated in the conductor, due to continuous operation, to be felt in the surrounding areas. These cables are widely used in aircraft cabling.

Cable Construction

  • Annealed tinned copper to IS:10241 Part 3, uniformly bunched to form a circular shape
  • Special core insulation HR-PVC 105°C
  • Braided with glass fiber, 100% coverage
  • Braided with nylon fiber, 100% coverage
  • Overall construction is finally lacquered with nylon varnish

Properties

  • Max. Operating Voltage: 600V r.m.s.
  • Operating Temperature Range: -35°C to 105°C
  • Resistant to ester-based fluids (hydraulic oil), acids, chemicals, and solvents.
  • The nylon and glass fibers are very good heat-resistant materials.

Cable Design Parameters

Part Number Cable Size Nom. Cross Sectional Area (mm²) No. & Dia. of Wires (mm) Max. Conductor Diameter (mm) Min. Conductor Diameter (mm) Min. PVC Insulation Radial Thickness Nylon Braid and Lacquer Max. (mm) Nylon Braid and Lacquer Min. (mm) Overall Diameter Max. (mm) Overall Diameter Min. (mm) DC Conductor Resistance at 20°C (Ω/km) Max. Current Rating (Amps) BS G 177
120401050001 14 2.05 70/0.193 1.956 1.803 0.279 0.178 0.076 3.4 3 9.2 31
120401060001 12 3.22 110/0.191 2.438 2.286 0.279 0.178 0.076 3.8 3.5 5.85 43
120401070001 10 5.33 73/0.305 3.15 2.896 0.381 0.381 0.127 5 4.6 3.532 61
120401080001 8 8.76 120/0.305 3.242 3.937 0.381 0.381 0.127 6.3 5.9 2.154 87
120401090001 6 13.3 182/0.305 5.537 5.08 0.381 0.381 0.127 7.6 7.3 1.422 115
120401100001 4 21.5 294/0.305 6.909 6.452 0.483 0.381 0.127 9.3 8.8 0.877 160
120401110001 2 33.3 203/0.457 8.763 8.128 0.483 0.381 0.127 11.0 10.5 0.565 200
120401120001 1 40.7 248/0.457 9.754 9.119 0.559 0.381 0.127 12.2 11.7 0.463 220
120401130001 0 53.0 323/0.457 10.973 10.338 0.635 0.381 0.127 13.7 13.0 0.355 240
120401140001 00 68.3 416/0.457 12.446 11.684 0.686 0.381 0.127 15.4 14.6 0.276 270

Table I: Current Ratings for Multiple Circuits

Note: * Denotes two cables only, ** Denotes five cables only

Cable Size Nominal Cross Sectional Area (mm²) Single Cable 3 – Bunched Cables 7 – Bunched Cables 12 – Bunched Cables
14 2.05 31 24 17 12
12 3.22 43 30 22 15
10 5.33 61 47 36 25
8 8.76 87 65 49 36
6 13.3 115 87 65
4 21.5 160 120 92
2 33.3 200 155 120
1 40.7 220 165 130
0 53 240 185 168*
00 68.3 270 210/240* 190**

Table II: Derating Factor of Uninyvin Cable for Different Ambient Temperature

Ambient temp. (°C) 40 45 50 55 60 65 70 75 80 85 90 95 100
Derating factor 1.0 0.96 0.92 0.88 0.83 0.78 0.75 0.73 0.68 0.62 0.53 0.48 0.3

Table III: Maximum 1 Minute Current Ratings for Multiple Circuits

Cable Size Nominal Cross Sectional Area (mm²) Single Cable 3 – Bunched Cables 7 – Bunched Cables 12 – Bunched Cables
14 2.05 50 47 43 42
12 3.22 72 67 62 60
10 5.33 110 107 104 101
8 8.76 173 165 159 153
6 13.3 250 236 230
4 21.5 390 378 360
2 33.3 545 530 520
1 40.7 620 600 590
0 53 705 690 680
00 68.3 820 810 800

Table IV: Fluid Resistance

Note: Uninyvin cables as per BS G 177 are meant for aircraft (cabling) flying under tropical weather conditions.

Sr. No. Fluid Represented Test Fluids Temp. of Test Max. Change in Dia. %
1 Aviation Turbine Fuel Kerosene 20 ± 0.5 5
2 Fuel 70% ISO Octane 30% Toluene by Vol. 20 ± 0.5 5
3 Hydraulic Fluid 80% Ethylene Glycol Mono Ethyl Ether, 20% Castor Oil by Vol. 50 ± 2 5
4 Ester Based Lubricating Oil Ester Based Hydraulic Fluid 100 ± 2 5