These cables are used in UPS systems and server rooms as the nylon and fiberglass braid on the cable does not allow the heat generated in the conductor, due to continuous operation, to be felt in the surrounding areas. These cables are widely used in aircraft cabling.
Cable Construction
Annealed tinned copper to IS:10241 Part 3, uniformly bunched to form a circular shape
Special core insulation HR-PVC 105°C
Braided with glass fiber, 100% coverage
Braided with nylon fiber, 100% coverage
Overall construction is finally lacquered with nylon varnish
Properties
Max. Operating Voltage: 600V r.m.s.
Operating Temperature Range: -35°C to 105°C
Resistant to ester-based fluids (hydraulic oil), acids, chemicals, and solvents.
The nylon and glass fibers are very good heat-resistant materials.
Cable Design Parameters
Part Number
Cable Size
Nom. Cross Sectional Area (mm²)
No. & Dia. of Wires (mm)
Max. Conductor Diameter (mm)
Min. Conductor Diameter (mm)
Min. PVC Insulation Radial Thickness
Nylon Braid and Lacquer Max. (mm)
Nylon Braid and Lacquer Min. (mm)
Overall Diameter Max. (mm)
Overall Diameter Min. (mm)
DC Conductor Resistance at 20°C (Ω/km)
Max. Current Rating (Amps) BS G 177
120401050001
14
2.05
70/0.193
1.956
1.803
0.279
0.178
0.076
3.4
3
9.2
31
120401060001
12
3.22
110/0.191
2.438
2.286
0.279
0.178
0.076
3.8
3.5
5.85
43
120401070001
10
5.33
73/0.305
3.15
2.896
0.381
0.381
0.127
5
4.6
3.532
61
120401080001
8
8.76
120/0.305
3.242
3.937
0.381
0.381
0.127
6.3
5.9
2.154
87
120401090001
6
13.3
182/0.305
5.537
5.08
0.381
0.381
0.127
7.6
7.3
1.422
115
120401100001
4
21.5
294/0.305
6.909
6.452
0.483
0.381
0.127
9.3
8.8
0.877
160
120401110001
2
33.3
203/0.457
8.763
8.128
0.483
0.381
0.127
11.0
10.5
0.565
200
120401120001
1
40.7
248/0.457
9.754
9.119
0.559
0.381
0.127
12.2
11.7
0.463
220
120401130001
0
53.0
323/0.457
10.973
10.338
0.635
0.381
0.127
13.7
13.0
0.355
240
120401140001
00
68.3
416/0.457
12.446
11.684
0.686
0.381
0.127
15.4
14.6
0.276
270
Table I: Current Ratings for Multiple Circuits
Note: * Denotes two cables only, ** Denotes five cables only
Cable Size
Nominal Cross Sectional Area (mm²)
Single Cable
3 – Bunched Cables
7 – Bunched Cables
12 – Bunched Cables
14
2.05
31
24
17
12
12
3.22
43
30
22
15
10
5.33
61
47
36
25
8
8.76
87
65
49
36
6
13.3
115
87
65
–
4
21.5
160
120
92
–
2
33.3
200
155
120
–
1
40.7
220
165
130
–
0
53
240
185
168*
–
00
68.3
270
210/240*
190**
–
Table II: Derating Factor of Uninyvin Cable for Different Ambient Temperature
Ambient temp. (°C)
40
45
50
55
60
65
70
75
80
85
90
95
100
Derating factor
1.0
0.96
0.92
0.88
0.83
0.78
0.75
0.73
0.68
0.62
0.53
0.48
0.3
Table III: Maximum 1 Minute Current Ratings for Multiple Circuits
Cable Size
Nominal Cross Sectional Area (mm²)
Single Cable
3 – Bunched Cables
7 – Bunched Cables
12 – Bunched Cables
14
2.05
50
47
43
42
12
3.22
72
67
62
60
10
5.33
110
107
104
101
8
8.76
173
165
159
153
6
13.3
250
236
230
–
4
21.5
390
378
360
–
2
33.3
545
530
520
–
1
40.7
620
600
590
–
0
53
705
690
680
–
00
68.3
820
810
800
–
Table IV: Fluid Resistance
Note: Uninyvin cables as per BS G 177 are meant for aircraft (cabling) flying under tropical weather conditions.